Safety instruction

1.Prior to operation, it is imperative that the water pump and the controller be correctly grounded. Failure to do so will expose users to a grave risk of electric shock.

2.Solar water pumps must be connected to our own controllers.It is strictly prohibited to test the pump without a controller. Otherwise, the motor will be burnt out.

3. It is strictly forbidden to connect wires when the power is on,otherwise there will be a risk of electric shock.

4.When the controller is running, it is strictly forbidden to touch or plug the power cord and output motor cord.

User Manual Download

Fault Information and Troubleshooting Method

Fault Code Fault Description Causes and Solutions of Fault Recovery Procedure
P0 Hardware Overcurrent •Motor model is mismatch, please choose matching pumps.
•UVW three-phase short-circuit connection, please rewiring to ensure the normal installation of UVW.
Automatically remove after 30s
P43 Phase Protection •UVW three-phase open circuit, please rewiring to ensure it reliable contact. Automaticallyremove after 30s
P46 Stall Protection •Motor model is mismatch, please choose matching pumps.
•Pump extension cord is too long, please reduce the extension cord.
 •Power is too low, increase the power supply.
 •Pump bearing is stuck, please clean pump bearings.
Automaticallyremove after 30s
P49 Software Overcurrent •Water pump bearing stuck, clean pump bearings.
•UVW three-phase short-circuit connection, please rewiring to ensure the normal installation of UVW.
Automaticallyremove after 30s
P50 Low Voltage Protection •The input voltage is too low, please distribute power refer to the electrical characteristics. Voltage return tonormal, remove the fault immediately
P51 High Voltage Protection •The input voltage is too high, please distribute power refer to the electrical characteristics. Voltage return tonormal, remove the fault immediately
P48 Dry-run Protection •Not all of air in the pump is exhausted, cut off the power, re-power and start the pump drainage after 30 seconds.
•There is no water in the water tank waiting for water, it will restart.
Automatically clear after 30 minutes or repower to clear
P60 High Temperature Protection •The temperature of controller MCU is more than 90°C. Automatically clear after the temperature is normal
E8 Current Sampling Failure •Cut off the power and restart after 30 seconds. Restart the power
PL Power Shortage •No sunlight, waiting for the sunlight to restart.
•Solar panel matching error, refer to the recommendation to match correctly.
At the first 5 times, it will removal after 30 seconds, and then 30 minutes to removal
ALARM Reverse connection protect •Exchange the positive and negative wire. Restart the power

Product maintenance video